8B-Voltage In/Out

Isolated Signal Conditioners for Backpanels

Voltage Input Modules, Narrow Bandwidth 3 Hz (8B30/8B31)

8B modules are an optimal solution for monitoring real-world process signals and providing high-level signals to a data acquisition system. Each 8B30/31 module isolates, filters, and amplifies a voltage input signal and provides an analog voltage output.

Signal filtering is accomplished with a 5-pole filter optimized for time and frequency response which provides 70 dB of normal-mode rejection at 60 Hz. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other four are on the system side.

A special input circuit on the 8B30 modules provides protection against accidental connection of power-line voltages up to 240 VAC. Clamp circuits on the I/O and power terminals protect against harmful transients.

Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from + 5 VDC, ± 5%.

The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.


Voltage Input Modules, 1kHz Bandwidth 1 kHz (8B40/8B41)

8B modules are an optimal solution for monitoring real-world process signals and providing high-level signals to a data acquisition system. Each 8B40/41 module isolates, filters, and amplifies a voltage input signal and provides an analog voltage output.

Signal filtering is accomplished with a 5-pole filter optimized for time and frequency response which provides 100 dB per decade of normal-mode rejection above 1 kHz. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other four are on the system side.

A special input circuit on the 8B40 modules provides protection against accidental connection of power-line voltages up to 240 VAC. Clamp circuits on the I/O and power terminals protect against harmful transients.

Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from + 5 VDC, ± 5%.

The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.


Voltage Output Modul 100 Hz (8B49)

8B modules are an optimal solution for monitoring real-world process signals and providing high-level signals to a data acquisition system. Each 8B49 module accepts an input signal from a non-isolated source, then isolates, filters and converts the signal to a high-level process voltage output.

Signal filtering is accomplished with a 4-pole filter optimized for time and frequency response which provides 80 dB per decade of normal-mode rejection above 100 Hz. One pole of this filter is on the system side and the other three are on the isolated field side.

A special output circuit in the 8B49 module provides protection against accidental connection of power-line voltages up to 40 VAC continuous. Clamp circuits on the I/O and power terminals protect against harmful transients.

The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.


Spannungseingangsmodul 20 kHz (8B50/8B51)

8B modules are an optimal solution for monitoring real-world process signals and providing high-level signals to a data acquisition system. Each 8B50/51 module isolates, filters, and amplifies a voltage input signal and provides an analog voltage output.

Signal filtering is accomplished with a 5-pole filter optimized for time and frequency response which provides 100 dB per decade of normal-mode rejection above 20 kHz. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other four are on the system side.

A special input circuit on the 8B50 or 8B51 modules provides protection against accidental connection of power-line voltages up to 240 VAC. Clamp circuits on the I/O and power terminals protect against harmful transients.

Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from + 5VDC, ± 5%.

The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.

PDF Downloads:



Specifications

top
  • Input mV- or V-Signal
  • Output: 0 V...+ 5V / 0 V...+ 10V / - 5V...+ 5V / - 10V...+ 10V
  • Bandwidth 3 Hz / 1 kHz / 100 Hz / 20 kHz / 15 kHz
  • Isolation 1500 Vrms
  • Input protection 240 VAC / ± 20 V
  • Input Resistance 50 MOhm / 500 kOhm (min.) / >= 1 MOhm
  • Accuracy ± 0.05%
  • Linearity ± 0.02%
  • ANSI/IEEE C37.90.1 Input protection
  • CMR 120dB / 100dB / 110dB
  • True 2-way isolation
  • NMR: 85dB at 60Hz / 100dB/Dec>1kHz / 80dB/Dec>100Hz / 100dB/Dec>20kHz
  • Power Supply +5 VDC
  • Operating Temperature Range -40°C … +85°C
  • Mix and Match Types on Backpanels possible
  • Dimensions 28.1 x 41.9 x 10.2 mm
  • Optional DIN Rail Mounting
  • CE Compliant
  • Wide range of accessories
  • Special Solutions on request