Current Output Modules, Bandwidth 100 Hz

8B modules are an optimal solution for monitoring real-world process signals and providing high-level signals to a data acquisition system. Each 8B39 module accepts an input signal from a non-isolated source, then isolates, filters, and converts the signal to an analog process current output.

Signal filtering is accomplished with a 3-pole filter optimized for time and frequency response which provides 60 dB per decade of normal-mode rejection above 100 Hz. One pole of this filter is on the system side and the other two are on the isolated field side.

A special output circuit in the 8B39 module provides protection against acciden-tal connection of power-line voltages up to 40 VAC continuous. Clamp circuits on the I/O and power terminals protect against harmful transients.

The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise.

Circuit diagram Dataforth SensorLex8B39

Block Diagram SensorLex8B39



PDF Downloads:

  • Product Overview SensorLex8B
  • Produkt Catalog SensorLex8B
  • Backpanels and Accessories

  • 5 Modules for Type SensorLex8B39:

    ModuleInputDescription
    8B39-01 0 V to +5 V SensorLex8B39 Isolated Current Output Module with Voltage- or Current-Input
    8B39-02 -5 V to +5 V SensorLex8B39 Isolated Current Output Module with Voltage- or Current-Input
    8B39-03 0 V to +5 V SensorLex8B39 Isolated Current Output Module with Voltage- or Current-Input
    8B39-04 -5 V to +5 V SensorLex8B39 Isolated Current Output Module with Voltage- or Current-Input
    8B39-07 -5 V to +5 V SensorLex8B39 Isolated Current Output Module with Voltage- or Current-Input

    Specifications

    top
    • Input: V-Signal
    • Output: 0...20 mA / 4...20 mA / -20...20 mA
    • Bandwidth 100 Hz
    • Isolation 1500 Vrms
    • Input protection 40 VAC
    • Input Resistance 50 MOhm
    • Accuracy ± 0.05%
    • Linearity ± 0.02%
    • ANSI/IEEE C37.90.1 Input protection
    • CMR 110dB
    • True 2-way isolation
    • NMR: 60dB / Decade > 100 Hz
    • Power Supply +5 VDC
    • Operating Temperature Range -40°C … +85°C
    • Mix and Match Types on Backpanels possible
    • Dimensions 28.1 x 41.9 x 10.2 mm
    • Optional DIN Rail Mounting
    • CE compliant, C-UL-US Listed
    • Wide range of accessories
    • Special Solutions on request