Current Output Signal Conditioners, Bandwidth 1 kHz

Each DSCA39 current output module provides a single channel of analog output. The input signal is buffered, isolated, filtered and converted to a unipolar or bipolar current output. Signal filtering is accomplished with a five-pole filter which provides 100 dB per decade of attenuation above 1 kHz. An anti-aliasing pole is located on the system side of the isolation barrier, and the other four poles are on the field side. After the initial system-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmis-sion of common mode spikes or surges.

Special output circuits provide protection against accidental connection of power-line voltages up to 240 VAC and against transient events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and power input terminals to guard against transient events and power reversal. Signal and power lines are secured to the module using screw terminals which are in pluggable terminal blocks for ease of system assembly and reconfiguration.

The modules have excellent stability over time and do not require recalibration, however, zero and span settings are adjustable up to ± 5% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.

Circuit diagram Dataforth DSCA39

Block Diagram DSCA39



PDF Downloads:


6 Modules for Type DSCA39:

ModuleInputDescription
DSCA39-01 0 V to +10 V DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input
DSCA39-02 -10 V to 10 V DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input
DSCA39-03 0 V to +10 V DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input
DSCA39-04 -10 V to 10 V DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input
DSCA39-05 4 mA to 20 mA DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input
DSCA39-07 -10 mA to 10 V DSCA39 Isolated Current Output Signal Conditioner with Voltage- or Current-Input

Specifications

top
  • Input: V-Signal
  • Output: 0 … 20 mA / 4 … 20 mA / -20 … +20 mA
  • Bandwidth 1 kHz
  • Isolation 1500 Vrms
  • Input protection ± 35 V
  • Input Resistance 2 MOhm
  • Accuracy ± 0.03%
  • Linearity ± 0.01%
  • ANSI/IEEE C37.90.1 Input protection
  • CMR 110dB
  • True 3-way isolation
  • NMR: 100dB / Decade > 1 kHz
  • Power Supply 15 to 30 VDC
  • Operating Temperature Range -40°C … +80°C
  • Adjustability of +/-5 % Zero and span
  • 5-pol. Filtering
  • Dimensions 75 x 22.5 x 105 mm
  • DIN Rail Mounting
  • CE and ATEX certified, C-UL-US compliant
  • Special Solutions on request