Search:
  Quote Basket  |  Sitemap  |  Imprint
  • Deutsch
  • English

SCM5B-Current In/Out

Isolated Signal Conditioners for Backpanels

Analog Current Input Modul 4 Hz (5B32)

Each SCM5B32 current input module provides a single channel of analog input which is filtered, isolated, amplified, and converted to a high-level analog voltage output. This voltage output is logic switch controlled, which allows these modules to share a common analog bus without the requirement of external multiplexers.

The SCM5B modules are designed with a completely isolated computer side circuit which can be floated to ± 50 V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch. If desired, the output switch can be turned on continuously by simply connecting pin 22, the Read-Enable pin, to I/O Common, pin 19.

A precision 20 Ω current conversion resistor is supplied with the SCM5B32 module. Sockets are provided on the SCMPB01/02/03/04/05/06/07 backpanels to allow installation of this resistor. Extra resistors are available under part number SCMXR1.

Signal filtering is accomplished with a six-pole filter which provides 95 dB of normal-mode rejection at 60 Hz and 90 dB at 50 Hz. Two poles of this filter are on the field side of the isolation barrier, and the other four are on the computer side.

After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges. The module is powered from +5 VDC, ± 5%.

A special input circuit on the SCM5B32 modules provides protection against accidental connection of power-line voltages up to 240 VAC.


Current Output Modul 400 Hz (5B39)

Each SCM5B39 current output module provides a single channel of analog output. The track-and-hold circuit in the input stage can be operated in a hold mode where one DAC can supply many output modules, or a track mode where one DAC is dedicated to each module. In addition to the track-and-hold circuit, each module provides signal buffering, isolation, filtering, and conversion to a high-level current output.

Setting of the track or hold mode is controlled by the logic state of WR EN\, module pin 23. When pin 23 is low, the track mode is enabled. If pin 23 is high, the hold mode is enabled. The module is designed with a completely isolated computer side circuit which can be floated to ± 50 V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the track and hold circuit. For a low state, simply connect pin 23, the Write-Enable pin, to I/O Common, pin 19.

The SCMPB02 and SCMPB06 backpanels allow host computer control of the WR EN\ control line, which allows multiplexing of one host DAC to up to 64 SCM5B39 output modules. During power-up, the output remains at 0 mA for 100 ms on all models except the SCM5B39-07, which allows the track-and-hold circuit to be initialized.

A special circuit in the output stage of the module provides protection against accidental connection of power-line voltages up to 240 VAC on all models.


Matched-Pair Servo/Motor Controller Modul 1 kHz (5B392)

The SCM5B392 servo/motor controller module set is designed to solve the problem of extending a servo or motor controller signal a long distance with the possibility for noise pickup and/or contacting hazardous voltages. Each SCM5B392 module set is made up of two modules: a voltage input/current output module and a current input/voltage output module.

The voltage input module connects to the servo or motor controller voltage output and provides an isolated 4 to 20 mA output which connects to the input of the current input module. The current input module isolates and provides an output voltage identical to that of the servo or motor controller. Thus the original control signal has been isolated (twice) and extended via a 4 to 20 mA current loop.

Several mounting options are available for the SCM5B392 module set. If a large number of channels are required, the SCMPB01 16 channel backpanel and SCMPB05 8 channel backpanel are available. Smaller channel numbers can be accommodated with the SCMPB03 single channel mounting panel and SCMPB04 dual channel mounting panel. These can be mounted on a DIN rail.


2-Wire Transmitter Interface Modul 100 Hz (5B42)

Each SCM5B42 2-wire transmitter interface module provides a single channel which accepts a 4 to 20 mA process current input and provides a standard + 1 to + 5 V or + 2 to + 10 V output signal . An isolated + 20 VDC regulated power supply is provided to power the current transmitter. This allows a 2-wire loop powered transmitter to be directly connected to the SCM5B42 without requiring an external power supply. The regulated supply will provide a nominal + 20 VDC at a loop current of 4 mA to 20 mA.

The SCM5B42 will provide a 1500 V isolation barrier for non-isolated 2-wire field transmitters. It can also be used when additional isolation is required between an isolated 2-wire transmitter and the input stage of the control room computer.

The voltage output is logic switch controlled, which allows these modules to share a common analog bus without the requirement of external multiplexers.

The SCM5B modules are designed with a completely isolated computer side circuit which can be floated to ± 50 V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch. If desired, the output switch can be turned on continuously by simply connecting pin 22, the Read-Enable pin, to I/O Common, pin 19.

A precision 20 Ω current conversion resistor is supplied with the module. Sockets are provided on the SCMPB01/02/03/04/05/06/07 backpanels to allow installation of this resistor. Extra resistors are available under part number SCMXR1. All field inputs are fully protected from accidental connection of power-line voltages up to 240 VAC. The module has a 3 dB bandwidth of 100 Hz. Signal filtering is accomplished with a six-pole filter, with two poles on the field side of the isolation barrier, and the other four on the computer side.

PDF Downloads:



Specifications

top
  • Input: mA- or V-Signal
  • Output: V 0…+5, +1…+5, 0…+10, +2…+10, ±5, ±10 / mA 0…20, 4…20, ±20
  • Bandwidth 4 Hz / 275 Hz / 400 Hz / 1 kHz / 100 Hz
  • Isolation 1500 Vrms
  • Input protection 240 Vrms
  • Input Resistance 20 Ohm / 50 od. 2 MOhm
  • Accuracy ± 0.03% / ± 0.05%
  • Linearity ± 0.005% / ± 0.03%
  • ANSI/IEEE C37.90.1 Input protection
  • CMR 160dB / 110dB / 100dB
  • True 3-way isolation
  • Sensor Excitation + 20 V (5B42)
  • Power Supply +5 VDC
  • Operating Temperature Range -40°C … +85°C
  • Mix and Match Types on Backpanels possible
  • Dimensions 58 x 57 x 15 mm
  • Optional DIN Rail Mounting
  • CSA certified, CE and ATEX compliant
  • Wide range of accessories